Description

Franklin Grid CG-ELS-HUB84CABLE
- Electrolyte Level Sensor Hub (with AC Power Adapter)
- Battery Strings: Up to 4 CG-ELS+ Sensor strings containing 2, 4, 6, and 8 Volt batteries
- Input configurations: Flexible Configuration, typically 24, 48, 110/120, 220/240, and 480 Volt systems
- ELS+ Sensor Arrangement: 600 CG-ELS+ Sensors per CG-ELS+ HUB with 150 maximum; CG-ELS+ Sensors for each of the 4 CG-ELS+ HUB inputs; Multiple CG-ELS+ HUB Inputs can be used on a single battery string to monitor all the cells within the battery string
- Alarm Output: 2 Form C Dry Contacts, 1A; Duplicate connector pins for alarm aggregation from multiple Hub units
Electrolyte Level Sensor Hub (with AC Power Adapter)
The CELLGUARD ELS+ Electrolyte Level Monitoring System provides reliable electrolyte level and temperature monitoring on Vented Lead Acid (VLA) batteries of any voltage, size, or design in Utility, Telecommunications, Data Centers, and Industrial Battery Plant applications.
Safe & Effective Vla Battery Monitoring
The CELLGUARD ELS+ Electrolyte Level Monitoring System is completely non-invasive to VLA batteries, delivers 24/7 monitoring of electrolyte levels, and enhances operational safety with battery case temperature alarming in the event of abnormal battery thermal conditions.


Monitoring Capabilities
During a low-level electrolyte level condition or if the battery case temperature limits are exceeded, the sensor communicates an alarm condition to the hub unit. The hub senses the alarm state and provides a dry contact alarmlead status.

Visual Alarm
Both the sensors and hub units provide LED indications to visually identify VLA batteries that require servicing.

Nerc PRC-005 Compliance
Complies with NERC PRC-005 electrolyte level inspection requirements with 24/7 alarm reporting

Easy Installation
Modular quick connect cabling provides time-saving installation without the need for a site survey.


Sensor Hub
The sensor string terminates into one common powering and alarming module hub. The hub aggregates all individual sensor alarms from all sensor strings to one common two form C dry contact interface and provides LED identification of the status of each string.


Reviews
There are no reviews yet.