Description
Autonics FXY Series Digital Counter/Timer Indicators

Counter and Timer, W72XH36mm, 6 Digit, LED, Indicator, (N)24-48VDC/24VAC
- Counting speeds: 1cps/30cps/2kcps/5kcps
- Switch between counter and timer operation using DIP switch
- Switch between voltage input (PNP) and no-voltage input (PNP) using DIP switch
Digital Counter/Timer Indicators (Indicator Only)
The FXY series indicators are counter/timer units with counting speeds of 1 cps, 30 cps, 2 kcps, and 5 kcps and various time setting ranges. Count-up, count-down, and count up/down modes are available for accurate measurement and display of various system configurations. The FXY series is available in 4-digit and 6-digit models in standard DIN size W 72 x H 36 mm.
| Model | Display digit | Size | Output | Power supply |
| FX4Y-I2 | 9999 (4-digit) | DIN W72×H36mm | Indicator | 24VAC 50/60Hz, 24-48VDC |
| FX4Y-I4 | 100-240VAC 50/60Hz | |||
| FX6Y-I2 | 999999 (6-digit) | 24VAC 50/60Hz, 24-48VDC | ||
| FX6Y-I4 | 100-240VAC 50/60Hz |
Connections

Dimensions

Proper Usage
- Follow instructions in ‘Proper Usage’. Otherwise, It may cause unexpected accidents.
- 24-48VDC, 24VAC power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
- Use the product, 0.1 sec after supplying power.
- When supplying or turning off the power, use a switch or etc. to avoid chattering.
- Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
- In case of contact input, set count speed to low speed mode (1cps or 30cps) to operate.
- If set to high speed mode (2kcps or 5kcps), counting error occurs due to chattering.
- Keep away from high voltage lines or power lines to prevent inductive noise.
- In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line.
- Do not use near the equipment which generates strong magnetic force or high frequency noise.
- This product may be used in the following environments.
① Indoors (in the environment condition rated in ‘Specifications’)
② Altitude max. 2,000m
③ Pollution degree 2
④ Installation category II