Description

Mastercool 55800
- Detects all refrigerants (CFC’s, HCFC’s, & HFC’s)
- Unit has been tested and approved to work with R1234yf as well as R32 and R410a
- Progressive LCD with vertical bars corresponding to the magnitude of the detected leak
INTELLASENSE Refrigerant Leak Detector
The 55800 leak detector employs a new metal oxide gas sensor for the detection of chlorofluorocarbon gasses and blends. This tin oxide sensor is characterized by high sensitivity and a fast response, upon detecting the presence of extremely small levels of chlorofluorocarbon gases. Integrated into the design is a powerful microprocessor that automatically selects the best-operating conditions for the sensor, to ensure optimum performance. The optimum sensor performance is maintained and monitored throughout the life of the sensor.
LCD FEATURES:
- WAIT: This indication flashes whenever the unit is in the wait mode. This could occur whenever the unit is turned on or interference is detected
- READY: This indication appears when the unit is ready for use
- INT: This indication appears whenever the microprocessor detects conditions that are not suitable for reliable leak detection. Excessive wind blowing, blocked probe (no air flow), burned out fan, or a missing or defective sensor that needs to be replaced
- BATTERY SYMBOL: When the battery symbol becomes illuminated this is an indication that the battery is low and needs to be replaced
- H – M – L: High, Medium and Low sensitivity ranges will be displayed accordingly based on the selection made on the keypad
- SIGNAL LEVEL BARS: There are 10 vertical signal level bars on the display corresponding to the level of signal detected by the unit
- ERROR SIGNALS: E1 through E9 indicates diagnostic signals
KEYPAD FUNCTIONS:
- ON/OFF: Press the ON/OFF button on the center of the keypad to turn the unit on or off
- VOLUME/MUTE: Press the VOLUME/MUTE button to control the volume of the unit
- H M L SENSITIVITY: Press the H M L SENSITIVITY button to select the desired sensitivity level
- HOLD: Press the HOLD button to freeze the signal bars. Press the HOLD button again to disengage
- PEAK: Press the PEAK button when multiple leaks are suspected as being present
HVAC Equipment and Instruments/Refrigerant HVAC/Refrigerant Leak Detectors Template | |
|---|---|
| Style (Refrigerant Leak Detectors) | Electronic |
| Refrigerant Detection | CFC, HCFC, HFC |
| Refrigerant Sensitivity | 0.15 oz/year |
| Alarm Sensitivity | 3 Level |
Product General Attributes | |
| Unique Features | Detects All Refrigerants, CFC’S, HCFC’S, HFC’S |
| Warranty | 1 YEARS |
| Warranty Details | MASTERCOOL Inc.® warrants this product against defects in material and workmanship for a period of one year (exceptions listed below) from date of purchase to original user. This warranty does not cover failure due to abuse, improper usage, neglect or progressive wear and tear. Warranty becomes valid to the original user when this form and proof of purchase is submitted within 30 days of purchase. Warranty service is provided through the factory only. Please contact the service department toll free for parts, |
| Data Logging | No |