Description

Eagle Eye VS-24
- Compliance with IEEE Std 450
- Compliance with National Fire Protection Agency (NFPA) Article 64
- Compliance with Uniform Building Code (UBC) Section 6400
- Automatic Operation and Continuous 24/7 Monitoring
- High Sensitivity and Stability
Hydrogen Gas Ventilation System
The VS-24 Hydrogen Gas Ventilation System is a forced ventilation fan system used in battery charging rooms and other areas where hydrogen may be present. This is to be used in conjunction with the HGD-2000 and HGD-3000 Hydrogen Gas Detectors. The hydrogen gas detector is mounted in the highest part of the room and the VS-24 vent fan is mounted through the outside wall.
The system has four fans factory-rated at 850 CFM each. This conforms to N+1 for 2550 CFM. The vent is equipped with a “Positive Airflow Shut Off” feature. These doors can be closed by an external electric command, and will stop any airflow from passing through the fans. The VS-24 is primarily set up to exhaust air but can be reversed to source forced air into a room.
Applications
- Utilities and Power Plants
- UPS Power Systems
- Fuel Cell Test Stations
- Nuclear Waste Reforming
- Hydrogen Refueling Stations
- Fire Department
- Battery Suppliers
- Battery Charging Rooms
- Motive Power
- Golf Cart
Optional Features
- Fan Supply Power: 24 VDC, 48 VDC, or 115 VAC
- Fan can be provided as an exhaust fan (standard) or supply fan (optional)
- Fan can be provided for -48 VDC A&B isolated redundant power service
- Fan can be provided with an optional firefighter shut down lever
- Fan can be provided with an optional emergency horn & flashing light
Product General Attributes | |
---|---|
Product Weight | 75 LBS |
Product Height | 24 IN |
Product Length | 18 IN |
Product Width | 24 IN |
Shipping Weight | 86.25 LBS |
HTS/Schedule B Number | 8414.59.9080 |
ECCN Number | EAR99 |
Country of Origin | United States |
Reviews
There are no reviews yet.