Description
Megger MIT210-EN – 1000V Digital/Analog Insulation and Continuity Tester

- Insulation tester for testing insulation resistance, voltage, and continuity in electrical installations
- Average-sensing meter provides accurate readings when measuring linear loads, where the current or voltage has a sinusoidal waveform
- Dual digital display with analog arc function to replicate response of analog meters
- Measures insulation resistance from 0 to 1,000 megohms, voltage from 25 to 600V, and continuity from 0.01 to 100 ohms
The Megger MIT210 1000 V Insulation and continuity tester is one of the smallest insulation testers available on the market today. With options of one, two and three voltage test voltage instruments, the Megger MIT210 instruments offer a range of safety and operation features.
The display of the Megger MIT210 offers a combination of digital readout and analog display, using Megger’s patented DART display technology, which includes the benefits of an LCD display, such as robust, clear and accurate measurement, with an analog pointer response for evaluating circuit charge and discharge characteristics.
The Megger MIT 210 housing is in tough ABS, designed to with-stand the rigorous of hard use, and is small enough to drop into your pocket when not in use. Battery requirements are 6 AA batteries of either standard alkaline or nickel metal hydride (NiMH) rechargeable type.
Continuity testing
Automatic continuity testing is performed at 200 mA to ensure compliance with international requirements. There is no need to press the test button.
The Megger MIT-210 will measure up to 100 Ω on continuity, of which 0-10 Ω is performed at greater than 200 mA to meet international electrical testing requirements. Lead null is possible up to 9.99 Ω of test lead resistance,ensuring the ability to null fused test leads as well as standard leads.
Continuity buzzer
A continuity buzzer provides a means of rapid cable testing and circuit identification, with voltage protection should you accidentally touch a live circuit. The buzzer operates at a 2 Ω threshold. The buzzer operates at a 2 Ω threshold.
Insulation testing
Insulation testing is possible up to 1000 Ω on all ranges. Auto discharge ensures all circuits are safely discharged after testing. The 1000 V insulation test range have a high voltage warning prior to test voltage being applied.
Safety
The Megger MIT210 Insulation and continuity tester is designed with safety as its primary objective. The Megger MIT/200 meets or exceed the requirements of safety directive IEC 61010 and EN61557 for insulation and continuity testing.
Default fault meter
A built-in voltmeter automatically switches in when the instrument is connected to a circuit with an AC or DC voltage greater than 25 V.
Insulation Test inhibit
Circuits in excess of 25 V will generate a voltage warning. Circuits over 50 V will inhibit testing of the insulation, protecting the operator and the Megger MIT210 from injury or damage.
600V CAT III
The Megger MIT210 Insulation and continuity tester has been designed for use on applications up to 600 V CAT III.
Applications
The Megger MIT-210 Insulation/continuity tester will find applications in electrical contracting, both on domestic and industrial systems, as well as site maintenance and service departments. The Megger MIT210 of insulation and continuity testers are ideal for testing transformers, motors, generators switch gear, panel building, domestic appliances, power tools etc., as well as fixed electrical wiring systems.
The Megger MIT-210’s small size and light weight make the Megger MIT210 ideal for those engineers that need to carry them for extended periods. All instruments meet the requirements of most International Standards including VDE0413 Part 1 and BS7671 (the 16th Edition of the IEE Wiring Regulations).
Micro / Milli / Meg Ohmmeters/Megohmmeter / Insulation Resistance Testers Template | |
---|---|
IR Test Voltage | 1,000 V |
Maximum Insulation Resistance | 1 G Ohms |
Type | Battery |
Minimum Insulation Resistance | 10 K Ohms (0.00001 G Ohms) |
Variable Incremental Voltage | No |
Display (Megohmmeter) | Digital Display (Megohmmeter) Digital display, with a responsive analog pointer emulation for evaluating circuit charge and discharge. |
Continuity Test | Yes Continuity Test Will measure up to 100Ω on continuity, of which 0-10Ω is performed at greater than 200 mA to meet international electrical testing requirements. |
Live Circuit Voltage Detection | Yes |
Power Supply | Battery Power Supply Uses 6 AA batteries. 3500 consecutive tests (5 seconds per test) on any test using 2Ah |
Timer | No |
CAT Rating | III |
CAT Voltage | 600 V |
Product General Attributes | |
Unique Features | Safety Every Megger instrument is designed with safety as its primary objective. All instruments meet or exceed the requirements of safety directive IEC 61010 and EN61557 for insulation and continuity testing.. Default fault meter 600V CATIII |
Warranty | 3 YEARSÂ Warranty Warranty – Extended warranty over 1 year is conditional on registering the product with Megger within 3 months of purchase. |
Safety Approval | CE |
IP Rating | IP40 |
Product Weight | 1.2 LBS |
Product Height | 1.6 IN |
Product Length | 7.7 IN |
Product Width | 3.9 IN |
Data Logging | No |
HTS/Schedule B Number | 9030332090 |
ECCN Number | 3A992 |
Calibration Included | Factory Calibration |
Battery Type | AA |
Power Supply Voltage | Battery Powered |
Country of Origin | United Kingdom |
Reviews