Description

Gossen Metrawatt M550S
- Test voltages in fixed increments, variable or as a ramp 50, 100, 250, 500, 1000 V
- Polarization index (PI) and dielelectric absorption ratio (DAR)
- Intelligent filter
- Signaling of dangerous contact voltage
- Acoustic signaling when limit value is exceeded
1000V Digital Insulation Tester, Resistance Measurement – 10Ohm to 10 kOhm
The METRISO XTRA insulation and resistance measuring instruments allow for quick and effective testing of protective measures in accordance with:
- DIN VDE 0100
- ÖVE-EN 1 (Austria)
- SEV 1000 (Switzerland)
- Regulations specific to other countries as well
- Insulation measurement per EN 61557-2 / VDE 0413 part 2
- Low-resistance measurement per EN 61557-4 / VDE 0413 part 4
- Voltage testing and measurement up to 1000V
- Backlit dot matrix display for measured and limit values
- Timer function 1 s … 100 min
- Guard terminal for compensating surface current
Measurements
- PI, DAR Polarization index measurements
- Riso Variable = 50 … 1000V (Limit value 1 MΩ)
- Riso VRamp = 50 … 1000V Display of breakdown voltage
- Measuring ranges
- Riso 10 k …1 TΩ
- Riso V = 50, 100, 250, 500 / 1000V
- R 10 Ω… 10 kΩ
- RLO 0,01 … 10 Ω
- V 0 … 500 / 1000V
Display functions
- Backlit display
- Limit value LED Limit (green/red)
- Additional acoustic signal, limit value per VDE 0100 Riso
- RLO LED for dangerous contact voltage (when switched off)
- LCD symbol for external voltage
- Battery level display
- Special functions
- Data storage in the instrument, 50.000 objects
- Discharge capacitive devices under test
- Safety shutdown (VBatt < 8 V)
Features
- Charging socket, RS232 and USB interface
- Measuring categories CAT II 1000V, CAT III 600V
- Measuring category CAT III 600V, CAT IV 300V
- Integrated 10 MΩ test resistor
- DAkkS calibration certificate
Applications
The insulation measuring instruments are suitable for the following tasks:
- Measurement of insulation resistance at voltage-free devices and systems, up to 1000V
- Testing of the resistance of earthing conductors, protective conductors and equipotential bonding
- Checking of test objects for the absence of voltage
- Testing of electrostatic discharge capacity at floor coverings (using shielded measurement cables) – EN 1081
- With the 1 mA test per DIN VDE 0845/EN 61645, the instrument also allows to perform on-site tests of the response voltage of overvoltage components (varistors, Zener diodes, etc.) of requirement categories B and C / SPD Type 2 and 3) and to evaluate the test results in accordance with manufacturer‘s data.
Micro / Milli / Meg Ohmmeters/Megohmmeter / Insulation Resistance Testers Template | |
|---|---|
| IR Test Voltage | 1,000 V, 100 V, 250 V, 50 V, 500 V |
| Maximum Insulation Resistance | 10 M Ohms (0.01 G Ohms) |
| Type | Battery |
| Display (Megohmmeter) | Digital |
| Power Supply | Battery |
| CAT Rating | IV |
| CAT Voltage | 300 V |
Product General Attributes | |
| Unique Features | Test voltage up to 1000 V, voltage measurement up to 1000 V. Low-resistance measurement, measurement of polarity and absorption index. |
| Safety Approval | CE |
| Interfaces I/O | RS-232, USB |
| IP Rating | IP40, IP52 |
| Product Weight | 1.5 KILOS (3.31 LBS) |
| Battery Type | AA |
| Power Supply Voltage | Battery Powered |
| Country of Origin | Germany |
| Other Information | Dimensions:: 225 x 130 x 140 mm |


Reviews
There are no reviews yet.